• Heat Shrinkable Anti-tracking Insulation Tubings for Cable Terminations

Heat Shrinkable Anti-tracking Insulation Tubings for Cable Terminations

DESCRIPTION

Features and Applications:
※Anti electrical tracking
※Heavy wall
※Semi flexible
※Excellent electrical properties
※UV and weather resistance
※Excellent creeping resistance
※Min. full recovery temp.: 110°C

Part No. Size (mm) As Supplied(mm) After Recovered (mm) Standard Length(mm)
D(Min.) d(Max.) w(Min.)
Continuous length tubing
D011201 BS10-30/10 30 10 2.8 15m/spool 30m/spool 1.0-1.5m
D011202 BS10-38/12 38 12 2.8 15m/spool 30m/spool 1.0-1.5m
D011203 BS10-43/14 43 14 2.9 15m/spool 30m/spool 1.0-1.5m
D011204 BS10-49/16 49 16 2.9 15m/spool 30m/spool 1.0-1.5m
D011205 BS10-55/18 55 18 3.0 15m/spool 30m/spool 1.0-1.5m
D011206 BS10-60/21 60 21 3.0 15m/spool 30m/spool 1.0-1.5m
D011207 BS10-70/26 70 26 3.1 15m/spool 30m/spool 1.0-1.5m
Cut length tubing
D011208 BS10-75/25 75 25 4.0 1000-1500mm
D011209 BS10-85/30 85 30 4.0 1000-1500mm
D011210 BS10-100/40 100 40 4.5 1000-1500mm

*D = Inner Diameter as supplied d = Inner Diameter after recovered
w = Wall Thickness after fully recovered

Technical properties:

Property Test Method Typical Data
Tensile strength ASTM D 2671 ≥11 MPa
Ultimate elongation ASTM D 2671 ≥400%
Longitudinal shrinkage ASTM D 2671 0 to -10%
Heat aging tensile strength Ultimate elongation 120℃, 168 hr. >10MPa >250%
Dielectric strength IEC 250 ≥15 kV/mm
Tracking resistance ASTM D 2303 /3.75 kV ,1 hr. Pass
Dielectric constant IEC 250 ≤3.0
Volume resistance ASTM D 2671 ≥1013 Ω*cm
Flammability (Oxygen Index ) IEC 4589 ≥25
Copper corrosion ASTM D 2671 No corrosion
Cold bend ASTM D 2671/-40℃,4 hr . No cracking
Water absorption ISO 62/23℃,14days <0.15%

Standard Colors:
※Red
Packaging:
※Standard packaging on spools.
※Special:1.0m, 1.22m, 1.50m pieces are available on request
※Other cut lengths are available, please contact us.