EDF Bimetallic AlCu Compression Cable Joints RJAU

※ Friction welding
※ Manufactured according to EDF HN 68 S 90
※ Material: Cu≥99.9%, Al≥99.5%
※ Surface: Bright

DESCRIPTION
Part No. Item Cross Section
Al/Cu mm²
Dimensions(mm)
D d d1 L1 L2 L
A060101 RJAU-16/16 16/16 16.0 6.0 6.0 42.0 40.0 91.0
A060102 RJAU-25/16 25/16 16.0 7.0 6.0 44.0 42.0 91.0
A060103 RJAU-25/25 25/25 16.0 8.0 7.5 44.0 42.0 91.0
A060104 RJAU-35/16 35/16 20.0 8.5 6.0 52.0 41.5 107.0
A060105 RJAU-35/25 35/25 20.0 8.5 7.0 52.0 41.5 107.0
A060106 RJAU-35/35 35/35 20.0 8.5 8.5 52.0 41.5 107.0
A060107 RJAU-50/25 50/25 20.0 9.7 7.0 52.0 41.5 107.0
A060108 RJAU-50/35 50/35 20.0 9.7 8.5 52.0 41.5 107.0
A060109 RJAU-50/50 50/50 20.0 9.7 9.7 52.0 41.5 107.0
A060110 RJAU-70/35 70/35 20.0 11.5 8.5 52.0 41.5 107.0
A060111 RJAU-70/50 70/50 20.0 11.5 9.7 52.0 41.5 107.0
A060112 RJAU-70/70 70/70 20.0 11.5 11.5 52.0 41.5 107.0
A060113 RJAU-95/35 95/35 20.0 13.5 8.5 52.0 41.5 107.0
A060114 RJAU-95/50 95/50 20.0 13.5 9.7 52.0 41.5 107.0
A060115 RJAU-95/70 95/70 20.0 13.5 11.5 65.0 46.0 133.0
A060116 RJAU-95/95 95/95 20.0 13.5 13.5 65.0 46.0 133.0
A060117 RJAU-120/50 120/50 25.0 15.0 9.7 65.0 46.0 133.0
A060118 RJAU-120/70 120/70 25.0 15.0 11.5 65.0 46.0 133.0
A060119 RJAU-120/95 120/95 25.0 15.0 13.5 65.0 46.0 133.0
A060120 RJAU-120/120 120/120 25.0 15.0 15.0 65.0 46.0 133.0
A060121 RJAU-150/50 150/50 25.0 16.5 9.7 65.0 46.0 133.0
A060122 RJAU-150/70 150/70 25.0 16.5 11.5 65.0 46.0 133.0
A060123 RJAU-150/95 150/95 25.0 16.5 13.5 65.0 46.0 133.0
A060124 RJAU-150/120 150/120 25.0 16.5 15.0 65.0 46.0 133.0
A060125 RJAU-150/150 150/150 25.0 16.5 16.5 65.0 46.0 133.0
A060126 RJAU-185/95 185/95 32.0 18.5 13.5 70.0 46.0 143.5
A060127 RJAU-185/120 185/120 32.0 18.5 15.0 70.0 46.0 143.5
A060128 RJAU-185/150 185/150 32.0 18.5 16.5 70.0 46.0 143.5
A060129 RJAU-185/185 185/185 32.0 18.5 18.5 70.0 46.0 143.5
A060130 RJAU-240/150 240/150 32.0 21.0 16.5 70.0 46.0 143.5
A060131 RJAU-240/185 240/185 32.0 21.0 18.5 70.0 46.0 143.5
A060132 RJAU-240/240 240/240 32.0 21.0 21.0 70.0 46.0 143.5
A060133 RJAU-300/240 300/240 40.0 23.0 21.0 80.0 78.0 180.0
A060134 RJAU-300/300 300/300 40.0 23.0 23.0 80.0 78.0 180.0
Application

In the wiring and electrical industry many types of wires and connectors are used for connecting electrical and mechanical equipments. The clamps or connectors used for connecting two electrical devices are called as electrical lugs. Use of cable lugs allows supply and distribution of electric current without any hindrance between electrical cables. Electrical lugs are used when permanent connection is not possible between devices or cables.

Use of cable lugs allows in easy installation, repair and maintenance of electrical devices or cables. Most common use of lugs includes connecting one cable with another cable or connection more than two cables. It is also used in connecting fuse sockets, load switches and electrical appliances, other than for connecting cables and power lines. To connect high voltage passing cables or electrical connections a special type of compression lug is used. As lugs are used for connecting electrical devices and cables, most of such connectors are available in rubber or plastic insulated sheets. This ensures safe handling.

Usually one end of the electrical lug is used for connecting a cable to an electrical device. This end is crimped or welded or soldered on the cable to ensure it is connected correctly and tightly. The other end of the lug is attached to the connection terminal of the electrical device. When connecting to the connection terminal, a bolt or screw is used to fasten it on it. Spring clip is used for connection purpose. Use of cable lugs differs based on usage and industry.

Cable lugs of various sizes, shapes, materials and configuration are used in the industry. In the wiring, automation, control panel and instrumentation industry, insulated lugs with pin terminal, blade terminal, hook terminal, fork terminal and ring terminal are used. For multiple connection purposes copper ring type lugs are commonly used. Many of the devices are connected with cables using Copper cable lugs.

Another type of lug is butt and parallel connector. This is mostly used for connecting and terminating 2 cables. Some of the widely used butt and parallel connectors are pvc insulated, butt type, heat shrinkable and closed end type. Most of the industries where cables are commonly used to connect equipments use butt and parallel connector. It is available in different sizes, shapes and materials Copper cable lugs are used as butt and parallel connector depending on the type of cable used to connect a device with the other.

In the power distribution industry, tube crimping lugs are used. As high voltage power is passed, most of the connectors used for connection purpose have a thick layer of insulation. Some use copper tubular lugs. Material of the lug should be chosen based on the usage.

In the wiring and electrical sector, lugs have indispensable usage. Strength of a lug should be checked before using it in the heavy-duty applications. In many applications the strength and the shape of lugs matters. Select lugs based on the usage.

Assembly

General Information

Compression connections require matching of compression cable lugs, conductors and tool size. That will provide best results: a durable, reliable connection.

Preparation

  • All compression cable lugs are stamped with cross section specification.
  • Select the compression tool die corresponding to this size.
  • The hexagon compressions are carried out by means of mechanical, hydraulic or electrical tools.
  • “Cu” marked dies have to be used for copper compression cable lugs.
  • “Al” dies are used for aluminum or aluminum alloy compression cable lugs.
  • In the case of hydraulic tools differentiation regarding the conductor materials is not necessary.

Assembly instruction:

  1. Strip conductor to sleeve length l+10%

       

  1. Remove all tapes/yarn/powder or similar conductor filling materials before mounting
  1. Erase dirt and oxide layers from both conductors using a metal brush
  1. Insert conductor into compression sleeve up to the stop or inspection hole
  1. Before compression verify the die code with the compression mark on the joint
  1. Start compression from the middle to the barrel end

     

  1. The number and position of the compression points is indicated by marking lines. Attention: All markings must be compressed
  1. Insert second conductor into compression sleeve up to the stop or inspection hole
  1. Start compression on second side from the middle to the barrel end

  1. Final Check: The extension length of the joint is about 10 % by proper compression with correct conductor – joint – die – combination
  1. Remove excess grease
Q & A

FREQUENTLY ASKED QUESTIONS


  • HOW ABOUT YOUR RAW MATERIAL?
    Conecteur use high-purity copper raw materials, better electrical conductivity, and better energy savings.
  • HOW TO CHOOSE FROM DIFFERENT TYPES?
    Different markets have different standards and habits, please refer to your local standard or contact us.
  • HOW ABOUT YOUR MACHINES?
    Automatic equipments effectively protect the stability of every parameters during production process, ensure a stable quality.
  • HOW ABOUT YOUR QUALITY?
    Sampling inspection of each process and finished-products, ensuring the quality reliability of each batch of products.
  • HOW ABOUT YOUR SURFACE TREATMENT?
    Avoiding oxidation on surface, both bright and dark tin-plated is aviable for terminal lugs and terminal connectors.
  • HOW TO CHOOSE CRIMPING TOOLS?
    Matching crimping tools and dies ensure good crimping quality and reliabe cable connection. KINGO supply related tools on request.